Whirlpool WGPH45 AM Installation Manual Page 10

  • Download
  • Add to my manuals
  • Print
  • Page
    / 20
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 9
10
System Troubleshooting
Symptom Possible Cause Remedy
High head—low suction Restriction in liquid line or flowrator Remove or replace with proper size flowrator.
High head—high or normal
suction
Dirty condenser coil
Overcharged
Condenser fan not running
Clean coil.
Correct system charge.
Repair or replace condenser fan.
Low head—high suction
Incorrect flowrator
Defective compressor valves
Flowrator not seating properly
Replace with correct flowrator.
Replace compressor.
Check for debris under flowrator or deformed flowrator.
Remove debris or replace flowrator.
Unit will not run.
Power off or loose electrical connection
Thermostat out of calibration; set too
high
Defective contactor
Blown fuses or tripped circuit breaker
Transformer defective
High or low pressure control (optional)
open
Compressor overload contacts open
Check for unit voltage at contactor in unit.
Reset thermostat.
Check for 24 volts at contactor coil. Replace if contacts
are open.
Replace fuse or reset circuit breaker. Check wiring.
Replace transformer.
Reset high pressure control or check unit charge.
High pressure control opens at 610 psig, and low
pressure control opens at 22 psig.
Replace compressor.
NOTE: Wait at least 2 hours for overload to reset.
Condenser fan runs;
compressor does not run.
Loose connection
Compressor stuck
Grounded or open winding
Open internal overload
Low voltage connection
Capacitor weak, open or shorted
Check for unit voltage at compressor.
Check and tighten all connections.
Wait at least 2 hours for overload to reset. If still open,
replace the compressor.
At compressor terminals, voltage must be within 10%
of nameplate volts when unit is operating.
Check capacitor. Replace if defective.
Low suction—Cool
compressor, iced evaporator
coil
Low indoor airflow Increase speed of blower or reduce restriction.
Replace air filters.
Compressor short cycles
Defective overload protector
Unit cycling on low pressure control
High pressure switch cuts out
Replace overload protector. Check for correct voltage.
Check refrigerant charge and/or airflow.
Check airflow (indoor and outdoor)
Registers sweat
Low airflow Increase speed of blower or reduce restriction.
Replace air filters.
High suction pressure
Excessive load
Defective compressor
Reversing valve not seating properly.
Recheck load calculation
Replace compressor.
Replace reversing valve.
Insufficient cooling
Improperly sized unit
Improper airflow
Incorrect refrigerant charge.
Incorrect voltage
Recalculate load.
Check airflow—should be approximately 400 CFM per
ton.
Charge per procedure attached to unit service panel.
At compressor terminals, voltage must be within 10%
of nameplate volts when unit is operating.
Evaporator coil freezing or
frosting
Low airflow
Low refrigerant charge
Operating unit in cooling mode below
65ºF (18ºC) outdoor temperature
Check airflow—should be approximately 400 CFM per
ton.
Properly charge unit.
Install or check low ambient control—should be open
below 65ºF (18ºC) outdoor temperature.
Page view 9
1 2 ... 5 6 7 8 9 10 11 12 13 14 15 ... 19 20

Comments to this Manuals

No comments