Whirlpool E2F30LD035V Use and Care Guide Page 6

  • Download
  • Add to my manuals
  • Print
  • Page
    / 36
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 5
6
Gas Supply
Gas Requirements
IMPORTANT: Read the data plate to be sure the water
heater is made for the type of gas you will be using in
your home. This information will be found on the data
plate located near the gas control valve/thermostat. If the
information does not agree with the type of gas available,
do not install or light. Call your dealer.
NOTE: An odorant is added by the gas supplier to the gas
used by this water heater. This odorant may fade over an
extended period of time. Do not depend upon this odorant
as an indication of leaking gas.
Gas Piping
The gas piping must be installed according to all local and
state codes or, in the absence of local and state codes, the
“National Fuel Gas Code”, ANSI Z223.1(NFPA 54)-latest
edition.
Tables 1 and 2 on the following page provide a sizing
reference for commonly used gas pipe materials. Consult
the “National Fuel Gas Code” for the recommended gas pipe
size of other materials.
Refer to Figure 3
NOTE: When installing gas piping, apply approved pipe joint
compound.
1. Install a readily accessible manual shut-off valve in the
gas supply line as recommended by the local utility.
Know the location of this valve and how to turn off the
gas to this unit.
2. Install a drip leg (if not already incorporated as part of
the water heater) as shown. The drip leg must be no
less than three inches long for the accumulation of dirt,
foreign material, and water droplets.
3. Install a ground joint union between the gas control
valve/thermostat and the manual shut-off valve. This
is to allow easy removal of the gas control valve/
thermostat.
4. Turn the gas supply on and check for leaks. Test all
connections by brushing on an approved noncorrosive
leak-detection solution. Bubbles will show a leak.
Correct any leak found.
Figure 3
Gas Piping
Manual Gas
Shut-off Valve
Ground
Joint
Union
3” minimum
Check with
local utility
for minimum height
Drip leg
6” Maximum
Air Gap
Discharge Pipe
(Do Not Cap
or Plug)
Floor Drain
Gas Pressure
IMPORTANT: The gas supply pressure must not exceed the
maximum supply pressure as stated on the water heaters data
plate. The minimum supply pressure is for the purpose of input
adjustment.
Gas Pressure Testing
IMPORTANT: This water heater and its gas connection must be
leak tested before placing the appliance in operation.
If the code requires the gas lines to be tested at a
pressure exceeding 14” W.C., the water heater and its
manual shut-off valve must be disconnected from the
gas supply piping system and the line capped.
If the gas lines are to be tested at a pressure less than
14” W.C., the water heater must be isolated from the
gas supply piping system by closing its manual shut-off
valve.
U.L. recognized fuel gas and carbon monoxide (CO) detectors are
recommended in all applications and should be installed using the
manufacturers instructions and local codes, rules, or regulations.
NOTE: Air may be present in the gas lines and could prevent
the burner from lighting on initial start-up. The gas lines should
be purged of air by a qualified person after installation of the gas
piping system. While purging the gas piping system of air, make
sure that the fuel is not spilled in the area of the water heater
installtion, or any source of ignition. If the fuel is spilled while
purging the piping system of air follow the “WHAT TO DO IF YOU
SMELL GAS” instructions on the cover of the manual.
Gas Pipe Capacity
Explosion Hazard
Use a new CSA approved gas supply line.
Install a shut-off valve.
Do not connect a natural gas water heater to
an L.P. gas supply.
Do not connect an L.P. gas water heater to a
natural gas supply.
Failure to follow these instructions can
result in death, explosion, or
carbon monoxide poisoning.
WARNING
Explosion Hazard
Have a qualified person make sure L.P. gas
pressure does not exceed 13” water column.
Examples of a qualified person include:
licensed plumbers, authorized gas company
personnel, and authorized service
personnel.
Failure to do so can result in death,
explosion, or fire.
WARNING
Page view 5
1 2 3 4 5 6 7 ... 36

Comments to this Manuals

No comments