I=Inspected NI=Not Inspected NP=Not Present D=Deficiency
I NI NP D
REI 7-2 (8/09) Page 26 of 41 J&R Inspect-It
The primary condensation drain line is located under the hall bathroom and master bathroom bathroom sink.
Make sure this sink remains clog free for proper HVAC operation.
Issues:
Plants/shrubs should be kept 18 inches from outside unit as not to interfere with the system; recommend
trimming or removing.
Upper Attic
Comments:
The downstairs A/C evaporator coil is Manufactured by AllStyle, Model No: ASFL3621A28E-V+S, Serial No:
7D17222S.
Note: Disassembly necessary to view the evaporator coils is beyond the scope of our inspection unless an access
door is installed. If the coil has not been serviced in the last year, we recommend that a licensed air conditioning
contractor review the system and make all corrections necessary to assure proper system operation.
The upstairs A/C evaporator coil is Manufactured by ASFL3621A28E-V+S, Model No: 7D17228S, Serial No:
7D17228S.
Note: Disassembly necessary to view the evaporator coils is beyond the scope of our inspection unless an access
door is installed. If the coil has not been serviced in the last year, we recommend that a licensed air conditioning
contractor review the system and make all corrections necessary to assure proper system operation.
The evaporator coil secondary overflow pan are installed and the drain line, exits over the upstairs and
downstairs window of the home. If water is ever seen draining from this line, it is an indication of a possible
problem with the primary drain or evaporator coil and a licensed HVAC contractor would need to be called for
an evaluation.
Float switch was not installed on the upstairs and downstairs evaporator secondary overflow pan. Although not
required, it is recommended to install switch to shut the A/C system off in the event the drain line for the
overflow pan becomes blocked and the pan fills with water. This will eventually overflow causing damage to
the ceiling.
Issues:
Recommend sealing gap around refrigerant line entrance to the upstairs evaporator coil to prevent loss of
conditioned air.