Whirlpool WGGE43 Instruction Manual Page 20

  • Download
  • Add to my manuals
  • Print
  • Page
    / 32
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 19
20
3. Remove the burners.
4. Use a bottle brush to clean burner insert and inside of the
burners.
5. Replace burners and manifold, inspect the burner assembly
for proper seating of burners in retention slots.
6. Reconnect electrical power and gas supply.
For further information on the yearly inspection, consult the User
Manual. It is recommended that a qualified servicer inspect and
service the unit at least once each year.
Turn the unit on at the thermostat. Wait a few minutes, since any
dislodged dust will alter the normal flame appearance. Flames
should be predominantly blue and directed into the tubes. They
should not be yellow. They should extend directly outward from
the burner ports without curling downward, floating or lifting off
the ports.
ACCESSORIES AND FUNCTIONAL PARTS
Sheet Metal Accessories
Additional accessories can be purchased to fit specific
application needs. Parts and instructions are available from your
distributor.
Functional Parts
General Information
Refer to the description in Functional Parts List when
ordering any of the listed functional parts. Be sure to provide
the unit model and serial numbers with the order.
Although only functional parts are shown, all sheet metal
parts, doors, etc., may be ordered by description.
Parts are available from your distributor.
APPENDIX
Blower Performance Data—Single Phase
Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and dangerous
operation. Verify proper operation after servicing.
WARNING
Always verify proper operation after servicing.
CAUTION
Functional Parts List
Auxiliary Limit Switch
Blower Housing
Circulator Blower Motor
Blower Wheel
Burner
Capacitor
Compressor
Flame Roll-out Switch
Flame Sensor
Gas Orifice
Gas Control Valve
Heat Exchanger
High Limit Switch
Igniter
Functional Parts List
Condenser Coil
Condenser Fan Blade
Condenser Fan Motor
Contactor
Gas Manifold
Evaporator Coil
Ignition Control
Induced Draft Blower
Pressure Switch
Pressure Switch Hose
Transformer
Unit Low Med High
Model Static CFM Watts Amps Rise CFM Watts Amps Rise CFM Watts Amps Rise
WGGE4324A045M
Rise Range:
30º to 60º
0.1 600 150 0.67 57 850 230 1.02 40 1,190 380 1.67 NR
0.2 570 140 0.65 60 830 220 1.00 41 1,140 360 1.62 NR
0.3 510 130 0.63 NR 765 215 0.97 45 1,080 350 1.58 32
0.4 450 125 0.61 NR 715 210 0.94 48 1,025 340 1.54 33
0.5 380 120 0.58 NR 660 205 0.90 52 975 330 1.38 35
0.6
--- --- --- NR 610 195 0.88 56 920 310 1.37 37
0.7
--- --- --- NR --- --- --- NR 830 300 1.35 41
0.8
--- --- --- NR --- --- --- NR 730 290 1.32 47
Page view 19
1 2 ... 15 16 17 18 19 20 21 22 23 24 25 ... 31 32

Comments to this Manuals

No comments