Whirlpool WGFD293 Instruction Manual Page 45

  • Download
  • Add to my manuals
  • Print
  • Page
    / 52
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 44
45
Induced draft
blower runs
continuously
with no further
furnace
operation.
Integrated
control module
LED display
provides “E2”
error code.
E2
Low-stage
pressure switch
circuit is not
closed.
Pressure switch
hose blocked,
pinched or
connected
improperly.
Blocked flue and/or
inlet air pipe,
blocked drain
system or weak
induced draft
blower.
Incorrect pressure
switch setpoint or
malfunctioning
switch contacts.
Loose or
improperly
connected wiring.
Inspect pressure
switch hose. Repair/
replace, if necessary,
Inspect flue and/or
inlet air piping for
blockage, proper
length, elbows and
termination.
Check drain system.
Correct as necessary.
Check induced draft
blower performance.
Correct as necessary.
Correct pressure
switch setpoint or
contact motion.
Tighten or correct
wiring connection.
Turn off power prior to
repair.
Replace pressure
switch with correct
replacement part.
Replace induced draft
blower with correct
replacement part.
Circulator
blower runs
continuously.
No furnace
operation.
Integrated
control module
LED display
provides “E3”
error code.
E3
Primary limit or
auxiliary limit
circuit is open.
Rollout limit
circuit is open.
Insufficient
conditioned air
over the heat
exchanger.
Blocked filters,
restrictive
ductwork, improper
circulator blower
speed, or failed
circulator blower.
Flame rollout.
Misaligned
burners, blocked
flue and/or air inlet
pipe or failed
induced draft
blower.
Loose or
improperly
connected wiring.
Check filters and
ductwork for blockage.
Clean filters or remove
obstruction.
Check circulator
blower speed and
performance. Correct
speed or replace
blower if necessary.
Check burners for
proper alignment.
Check flue and air inlet
piping for blockage,
proper length, elbows
and termination.
Correct as necessary.
Check induced draft
blower for proper
performance. Replace,
if necessary.
Tighten or correct
wiring connection.
Turn off power prior to
repair.
See Specification
Sheet applicable to
your model for
allowable rise range
and proper circulator
speed.
See “Vent/Flue Pipe”
section for piping
details.
Induced draft
blower and
circulator
blower runs
continuously.
No furnace
operation.
Integrated
control module
LED display
provides “E4”
error code.
E4
Flame sensed
with no call for
heat.
Short to ground in
flame sense circuit.
Lingering burner
flame.
Slow closing gas
control valve.
Correct short at flame
sensor or in flame
sensor wiring.
Check for lingering
flame.
Verify proper operation
of gas control valve
Turn off power prior to
repair.
No furnace
operation.
Integrated
control module
LED display
provides “E5”
error code.
E5
Open fuse. Short in low voltage
wiring.
Locate and correct
short in low voltage
wiring.
Turn off power prior to
repair.
Replace fuse with 3A
automotive fuse.
Symptoms of
Abnormal
Operation
Diagnostic/
Staus LED
Code Fault Description Possible Causes Corrective Actions Notes and Cautions