Whirlpool ED5FHAXVB00 Instruction Manual Page 6

  • Download
  • Add to my manuals
  • Print
  • Page
    / 8
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 5
6
3. Install a 3 in. trap in both the primary and secondary drain
lines as close to the unit as practical. Make sure the top of the
trap is below the connection to the drain pan to allow
complete drainage of the pan.
NOTE: Horizontal runs over 15 ft long must also have an anti-
siphon air vent (standpipe) installed ahead of the horizontal
run. See Typical Condensate Drain Connection. An
extremely long horizontal run may require an oversized drain
line to eliminate air trapping.
Typical Condensate Drain Connection
(secondary drain not shown)
NOTE: Do not install evaporator coil without a drain trap. The
condensate drain is on the negative pressure side of the blower;
therefore, air being pulled through the condensate line will
prevent positive drainage without a proper trap.
4. Route the drain line to the outside or to an appropriate drain.
Drain lines must be installed so they do not block service
access to the front of the evaporator coil. A 24 in. clearance is
required for filter, coil, or blower removal and service access.
NOTE: Check local codes before connecting the drain line to
an existing drainage system.
5. Insulate the drain lines where sweating could cause water
damage.
Test condensate drain pan and drain line after installation:
1. Pour several quarts of water into drain pan, enough to fill
drain trap and line.
2. Check to make sure the drain pan is draining completely, no
leaks are found in drain line fittings, and water is draining
from the end of the primary drain line.
3. Correct any leaks found.
Connect Refrigerant Lines
Refrigerant lines must be connected by a licensed, EPA certified
refrigerant technician in accordance with established procedures.
IMPORTANT:
Connecting refrigerant lines must be clean, dehydrated,
refrigerant-grade copper lines. Evaporator coils should be
installed only with specified line sizes for approved system
combinations.
Use care with the refrigerant lines during the installation process.
Sharp bends or possible kinking in the lines will cause a
restriction.
Do not remove the caps from the lines or system connection
points until connections are ready to be completed.
1. Route the suction and liquid lines from the fittings on the
indoor coil to the fittings on the outdoor unit. Run the lines in
as direct a path as possible, avoiding unnecessary turns and
bends.
2. Ensure that the suction line is insulated over the entire
exposed length and that both suction and liquid lines are not
in direct contact with floors, walls, duct work, floor joists, or
other piping.
3. Connect the suction and liquid lines to the evaporator coil.
4. To avoid damaging the rubber grommets in the cabinet while
brazing, slide the rubber grommets over the refrigerant lines
until they are away from the heat source.
5. Braze with an alloy of silver or copper and phosphorus with a
melting point above 1,100°F.
NOTE: Do not use soft solder.
6. Reinstall the rubber grommets after brazing is finished.
7. Make sure outdoor unit has been put in place according to
the Installation Instructions and is connected to the
refrigerant lines.
ASSISTANCE OR SERVICE
If you need further assistance, you can write to the below
address with any questions or concerns:
Whirlpool
®
Home Cooling and Heating
7901 S.W. 6th Court
Plantation, Florida 33324
Please include a daytime phone number in your correspondence.
Accessories
To order accessories, ask for the appropriate part number listed
below or contact your Whirlpool
®
Home Cooling and Heating
dealer.
1. Evaporator coil
2. Drain connection
3. Drain line
4. Anti-siphon air vent (for horizontal
runs of 15 ft or longer)
5. Drain trap
3.00" Min.
1.00" Min.
12.00"
Max.
1
2
4
5
3
ACFAIRSEAL-1 Air Seals (4) - for 2 installations
Page view 5
1 2 3 4 5 6 7 8

Comments to this Manuals

No comments