1. Check to see if all supply and return air grilles are adjusted
and the air distribution system is balanced for the best
compromise between heating and cooling.
2. Check for air leaks in the ductwork. See “Airflow
Measurement and Adjustment” and “Checking Charge.”
3. Make sure that the unit is free of “rattles,” and the tubing in
the unit is free from excessive vibration.
4. Make sure that the tubes and lines are not rubbing against
each other or against the sheet metal surfaces or edges. If
contact is found, correct the trouble.
5. Set the thermostat at the appropriate setting for cooling and
heating or automatic changeover for normal use.
6. Check that the owner is instructed on the unit operation, filter,
servicing, correct thermostat operation, etc.
7. The previous sections are recommended to serve as an
indication that the unit will operate normally.
COMPONENTS
Contactor
This control is activated (closed) by the room thermostat for both
heating and cooling. The contactor has a 24-volt coil and
supplies power to the compressor and outdoor fan motor.
Crankcase Heater
This item is “ON” whenever power is supplied to the unit. It
warms the compressor crankcase thereby preventing liquid
migration and subsequent compressor damage. The insert type
heater is self-regulating. It is connected electrically to the
contactor L1 and L2 terminals.
Condenser Motor
This item is activated by the contactor during heating and
cooling, except during defrost and emergency heat operation.
Compressor
This item is activated by the contactor for heating and cooling,
except during emergency heat. It is protected by an internal
overload.
Contactor Relay
This control is activated by the thermostat (24-volt coil) and
supplies power to the contactor.
Defrost Control
The Defrost control provides time/temperature initiation and
termination of the defrost cycle. When a defrost cycle is initiated,
the defrost control shifts the reversing valve to Cooling mode,
stops the outdoor fan and brings on supplemental heat.
Normally, a defrost cycle will take only 2 to 3 minutes unless the
system is low on charge or outdoor conditions are severe (windy
and cold).
Outdoor Thermostat
These optional controls are used to prevent full electric heater
operation at varying outdoor ambient (0°F to 45°F [-18ºC to 7ºC]).
They are normally open above their set points and closed below
to permit staging of the indoor supplement heater operation. If
the outdoor ambient temperature is below 0° F (-18°C) with 50%
or higher relative humidity (RH), an outdoor thermostat (OT) must
be installed and set at (0°) on the dial. Failure to comply with this
requirement may result in damage to the product which may not
be covered by the manufacturer’s warranty.
Reversing Valve Coil
This coil is activated by the thermostat in the cooling mode and
during defrost. It positions the reversing valve pilot valve for
cooling operation.
Indoor Blower Motor
This is activated by setting the room thermostat to COOLING/
HEATING or FAN ON position. The motor is energized through
the EBTDR for PSC motors.
The X-13 motors are activated by setting the room thermostat to
COOLING/HEATING or FAN ON position. The motor is energized
by a 24-volt control signal (from thermostat Y, G or W). X-13
motors are constant torque motors with very low power
consumption. See “Airflow Measurement and Adjustment” for
speed adjustment instructions.
Blower Interlock Relay
This relay is used to energize the blower during the electric heat
operation. Some room thermostats do not energize the motor
during electric heat. This relay ensures blower operation when
the room thermostat energizes heat. This relay has a 240-volt coil
and an 8-amp contact relay. This relay is energized by the electric
heat kit sequencer.