The connection between an indoor unit and an
outdoor unit.
Unscrew the flare nut for releasing pressure gas
in the indoor unit. If there is no high pressure gas
blowing out, it is the signal of a leaking indoor
unit.
Fit the flare nut to the liquid pipe. Flare the pipes
and with flare tool.
Tighten both flare nuts into gas pipe and liquid
pipe at the indoor unit with two holding spanners.
AIR PURGING
The purpose of air purging is to get rid of moisture and air in the system, otherwise moisture and air may
cause ineffectiveness of the compressor which directly affects the cooling capacity.
PURGING BY USING VACUUM
After tightening the flare nuts between the indoor and
the outdoor units.
Remove a blank cap of a three-way valve by using a
torque wrench. Check if both high pressure and
low pressure valve are in closed condition.
Remove the nut of the service port.
Connect a gauge into the service port and vacuum
port and vacuum pump.
Vacuum until the gauge indicates at 30 inches
mercury pressure.
Remove gauge. Tighten up the nut of the service
port.
Use a hexagonal wrench to open both high
pressure and low pressure valves to the end (counter clockwise).
Tighten the blank cap of the three-way valve.
GAS LEAKING CHECK
Check leakage by apply soapsuds to every
connection and inspect carefully. After checking,
wipe them off completely.
Cover indoor unit joint with pipe insulation and 4
plastic bands to prevent condensation at joints.
Connecting wire
Liquid pipe
Diameter Drain Pipe ½
Piping tape
Gas tape
Point at 30 inches
mercury pressure
Open
Close
Vacuum pump
OUTDOOR UNIT
Gauge