2.5. Auxiliary Heat (Duct Heater), If Required
In certain climates or regions and with some pool enclosures, construction materials,
additional supplemental room heat is required, then an electric duct heater, duct furnace
or hot water coil should be installed down stream in the supply air duct system of the
DryAire dehumidifier.
When a duct heater (field supplied) is required to supply supplemental or auxiliary heat to
satisfy the total heat loss of the pool area refer to equipment 24v wiring diagram attached
to inside of electrical panel.
2.6. Outdoor Installation
When the dehumidifier is located outdoors, or in an un-conditioned space where ambient
temperatures can fall below 45°F, such as an attic, you must use an outdoor-rated
dehumidifier (optional features) to included weatherproofing and thicker insulation. Special
precautions must be taken with the condensate drain pan and piping to prevent winter
freeze up.
Contractor must heat tape the condensate drain pan, P-trap and all exposed drain piping
connections. Heat tape to have exterior power source from DryAire dehumidifier.
The blower indicator switch on the automatic thermostat must be set in the “ON” position
which will allow the system blower to run continuously. This will circulate 80°F room air
through the dehumidifier during the winter season.
Figure 2.5.1. Duct Heater Location
15 DryAire Systems
2
4
/
3
0
M
IN.