11.2. Dehumidifier Off
DEHUMIDIFIER OFF
{CONTACTOR CLOSED}
COMPRESSOR HUMS DOES NOT HUM
• Refrigerant pressure not equalized. • Contactor points burned.
• Run capacitor open. • Compressor wiring open.
• Compressor wiring open. • Thermal overload open.
• Three phase compressor stuck
on single phasing.
DEHUMIDIFIER SHORT CYCLES
• Low charge. • Low suction pressure. Normal Suction
• DX valve power element. • Suction too warm. • Low voltage.
• Dryer restricted. • Unbalanced phase.
• Low air flow. • Tight compressor.
High Suction
• Bad compressor.
• Blower set for too
much air flow.
• Dirty filter. • Over-charged.
• Slow blower speed. • Air in system.
• Room temperature too • Dirty filter.
high. • Short cycling air.
• Supply or return air • Low air flow.
grilles restricted. • Return air temperature
• Defective high pressure above 90°F.
switch.
LOW PRESSURE
CONTROL
HI-PRESS SWITCH
TRIPPING / REPEAT
HI-PRESS SWITCH
TRIPPING / REPEAT
COMPRESSOR
THERMOSTAT
THERMAL
OVERLOAD