11.2. Dehumidifier Off
DEHUMIDIFIER OFF
{CONTACTOR CLOSED}
COMPRESSOR HUMS DOES NOT HUM
Refrigerant pressure not equalized. Contactor points burned.
Run capacitor open. Compressor wiring open.
Compressor wiring open. Thermal overload open.
Three phase compressor stuck
on single phasing.
DEHUMIDIFIER SHORT CYCLES
Low charge. Low suction pressure. Normal Suction
DX valve power element. Suction too warm. Low voltage.
Dryer restricted. Unbalanced phase.
Low air flow. Tight compressor.
High Suction
Bad compressor.
Blower set for too
much air flow.
Dirty filter. Over-charged.
Slow blower speed. Air in system.
Room temperature too Dirty filter.
high. Short cycling air.
Supply or return air Low air flow.
grilles restricted. Return air temperature
Defective high pressure above 90°F.
switch.
LOW PRESSURE
CONTROL
HI-PRESS SWITCH
TRIPPING / REPEAT
HI-PRESS SWITCH
TRIPPING / REPEAT
COMPRESSOR
THERMOSTAT
THERMAL
OVERLOAD
33 DryAire Systems