Do not install a standard dehumidifier in an unconditioned space or
where ambient temperatures can fall below 45°F.
If you must install the dehumidifier outside or in an unconditioned space, such as an attic,
you must use an outdoor rated dehumidifier. DryAire equips all outdoor rated dehumidifiers
with proper weatherproofing and thicker insulation. A label located on the electrical panel
door will identify an outdoor prep dehumidifier. (See Section 2.6 for details).
1.5. High Voltage Electrical Connections
THE INSTALLING CONTRACTOR MUST VERIFY THAT ALL ELECTRICAL WIRING
TO THE DEHUMIDIFIER AND ITS ACCESSORIES COMPLIES WITH NATIONAL, STATE
AND LOCAL CODES.
1.5.1. Wire and Fuse Sizing
The field-installed power supply wires and over current devices must be sized to
handle the minimum ampacity of the dehumidifier without exceeding the maximum
fuse size rating. Both the minimum ampacity and the maximum fuse size are listed
on the unit rating plate.
The grounding wire size must be the same or larger than the supply wire size.
Provide an uninterrupted grounding source to prevent the possibility of injury.
Failure to properly wire the dehumidifier will create the possibility of
electrical shock and may ultimately lead to premature system failure.
CEILING SUSPENDED
INSTALLATION
Figure 1-A.
7 DryAire Systems