4.0. Head Pressure Controller / Remote Condenser
The capacity of an air cooled condenser will vary with the difference between the entering air dry bulb
temperature and the condensing temperature of the refrigerant. The low ambient control will insure the
condensing temperature is sufficiently high enough for proper operation of the refrigerant expansion
valve during low ambient conditions.
4.1. Low Ambient Head Pressure Control
With outdoor temperature 32°F and below, the DryAire remote outdoor condenser will con-
tinue to operate efficiently. As an added feature on industrial and commercial models, the
DryAire system has equipped the remote outdoor condenser with an automatic head pres-
sure controller to operate at just the right pressure when low ambient temperatures exist.
This remote outdoor condenser head pressure control is provided to vary the air flow through
the condenser using a fan cycling method during low ambient conditions.
This low ambient control is factory installed and pre-set. In most cases, field adjustment
should not be required.
Settings: “On” @ 150 psi / “Off” @ 100 psi
5.0. System Air Flow
Proper unit air flow is critical to the overall performance of dehumidification systems. Be sure to
check the static pressure requirements and design limitations of both pieces of equipment for
proper installation and operation.
All DryAire Series dehumidifiers are shipped from the factory with the external static pressure adjust-
ed at a range of 0.10" to 1.0" w/c. A different motor pulley, flywheel or motor of another horsepower
rating may be required to achieve 1.0" ESP or desired external static pressure.
5.1. Excessive Air Flow Problems.
1. High amp draw on blower motor.
2. Decrease in moisture removal capacity.
3. Excessive unit noise.
4. Water Carry-over from evaporator coil.
DryAire Systems 24
OUTDOOR REMOTE CONDENSER
LOW AMBIENT CONTROLLER
Differential Screw
Differential Pointer
Bellows
Range Screw
Manual Reset Button
Not Available On All Models
Cover Screw
IMPORTANT: DO NOT FIELD ADJUST LOW
AMBIENT CONTROLLER.
CONTACT FACTORY
FACTORY SET: “ON” @ 150 PSI
“OFF” @ 100 PSI
DIFFERENTIAL 50 PSI