Whirlpool WPIO-369B Instruction Manual Page 18

  • Download
  • Add to my manuals
  • Print
  • Page
    / 40
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 17
18
Gas Piping Connections
When sizing a trunk line, be sure to include all appliances which
will operate simultaneously.
The gas piping supplying the furnace must be properly sized
based on the gas flow required, specific gravity of the gas and
the length of the run. The gas line installation must comply with
local codes, or in their absence, with the latest edition of the
National Fuel Gas Code, NFPA 54/ANSI Z223.1.
Pressure 0.5 psig or less and pressure drop of 0.3" W.C.; based
on 0.60 specific gravity gas
To connect the furnace to the building’s gas piping, the installer
must supply a ground joint union, drip leg, manual shutoff valve
and line and fittings to connect to the gas control valve. In some
cases, the installer may also need to supply a transition piece
from ¹⁄₂" (1.3 cm) pipe to a larger pipe size.
The following stipulations apply when connecting gas piping.
Use black iron or steel pipe and fittings for building piping.
Use pipe joint compound (pipe dope) on male threads only.
Always use pipe joint compound (pipe dope) that is approved
for all gases.
NOTE: Do not apply compound to the first 2 threads.
Use ground joint unions.
Install a drip leg to trap dirt and moisture before it can enter
the gas control valve.
NOTE: The drip leg must be a minimum of 3" (7.6 cm) long.
Install a ¹⁄₈" NPT pipe plug fitting, accessible for test gage
connection, immediately upstream of the gas supply
connection to the furnace.
Use 2 pipe wrenches when making the connection to the gas
control valve to keep it from turning.
NOTE: The orientation of the gas control valve on the
manifold must be maintained as shipped from the factory.
Install a manual shutoff valve between the gas meter and the
furnace within 6 ft (1.8 m) of the furnace.
If a union is installed, the union must be downstream of the
manual shutoff valve, between the shutoff valve and the
furnace.
Tighten all joints securely.
Connect the furnace to the building piping by one of the
following methods:
1. Rigid metallic pipe and fittings.
2. Semirigid metallic tubing and metallic fittings.
NOTE: Aluminum alloy tubing must not be used in exterior
locations.
Use UL Listed/CSA approved gas appliance connectors in
accordance with their instructions.
Gas connectors must be fully in the same room as the
furnace.
Protect gas connectors and semirigid tubing against physical
and thermal damage when installed.
Ensure that aluminum alloy tubing and connectors are coated
to protect against external corrosion when in contact with
masonry, plaster, insulation or subjected to repeated wetting
by liquids such as water (except rain water), detergents or
sewage.
General Furnace Layout
Upflow Installations
When the gas piping enters through the right side of the furnace,
the installer must supply the following fittings (starting from the
gas control valve):
90º elbows (2)
Close nipple
Straight pipe to reach the exterior of the furnace
Ground joint union
Natural Gas Capacity of Pipe—Cu ft of Gas Per Hour
(CFH)
Length of
Pipe—
ft (m)
Nominal Black Pipe Size
¹⁄₂ " ³⁄₄ "1" 1¹⁄₄ "1¹⁄₂ "
10 (3) 132 278 520 1,050 1,600
20 (6.1) 92 190 350 730 1,100
30 (9.2) 73 152 285 590 980
40 (12.2) 63 130 245 500 760
50 (15.2) 56 115 215 440 670
60 (18.3) 50 105 195 400 610
70 (21.3) 46 96 180 370 560
80 (24.4) 43 90 170 350 530
90 (27.4) 40 84 160 320 490
100 (30.5) 38 79 150 305 460
CFH =
Btu/h Furnace Input
Heating Value of Gas (Btu/cu ft)
Goodman 62
To avoid possible unsatisfactory operation or equipment
damage due to underfiring of equipment, use the proper
size of Natural/propane gas piping needed when running
pipe from the meter/tank to the furnace.
CAUTION
A. Manual shutoff valve location
(upstream of ground joint pipe union)
B. Height required by local codes
C. Ground joint pipe union (upstream of
gas control valve)
D. Drip leg
E. Reducing coupling—
¹⁄₂
" x
¹⁄₈
"
with
¹⁄₈
" pipe plug to
measure line gas pressure
Furnace Layout
G 2009
‘‘
A
B
C
D
E
Page view 17
1 2 ... 13 14 15 16 17 18 19 20 21 22 23 ... 39 40

Comments to this Manuals

No comments