Whirlpool WPIO-369B Instruction Manual Page 28

  • Download
  • Add to my manuals
  • Print
  • Page
    / 40
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 27
28
If the thermostat call is for low heat, the gas control valve and
induced draft blower will continue on low stage. If the call is
for high heat, the gas control valve and induced draft blower
will change to high stage.
Circulator blower is energized on heat speed following a fixed
30-second blower-on delay. The circulator blower requires
30 seconds to ramp up to full speed. Electronic air cleaner
terminal is energized with circulator blower.
Furnace is now operating on the specified stage called for by
the 2-stage thermostat.
Furnace runs, integrated control module monitors safety
circuits continuously.
If the 2-stage thermostat changes the call from low heat to
high heat, the integrated control module will immediately
switch the induced draft blower, gas control valve and
circulator blower to their high-stage settings.
If the 2-stage thermostat changes the call from high heat to
low heat, the integrated control module will immediately
switch the induced draft blower and gas control valve to their
low-stage settings. The circulator blower will remain on
high-heating speed for 30 seconds before switching to the
low-heat circulating speed.
R and W1 (or R and W1/W2) thermostat contacts open,
completing the call for heat.
Gas control valve closes, extinguishing flame.
Induced draft blower is de-energized following a 15-second
post purge. Humidifier terminal is de-energized.
Circulator blower continues running for the selected heat-off
delay period (90, 120, 150 or 180 seconds). The speed run
during this period depends on the last heat call provided by
the thermostat. If the last call for heat was a call for low heat,
the air circulator motor will run on low heat speed for the
duration of the heat-off delay period (90, 120, 150 or
180 seconds). If the last call for heat was a call for high heat,
the air circulating motor will run on the high heating speed for
30 seconds and then switch to the low-heating speed for the
balance of the heat-off delay period (60, 90, 120 or
150 seconds).
Circulator blower and electronic air cleaner terminals are de-
energized.
Circulator blower ramps down to Off during the 30 seconds
following the heat-off delay period.
Furnace awaits next call from thermostat.
Cooling Mode
The normal operational sequence in cooling mode is as follows:
R and Y1/G or Y2/G thermostat contacts close, initiating a
call for cool.
Integrated control module performs safety circuit checks.
Outdoor fan and compressor are energized to their
appropriate speeds.
Circulator blower is energized on the appropriate cool speed
at the level and time determined by the selected ramping
profile. Electronic air cleaner terminals are energized with
circulator blower.
Furnace circulator blower and outdoor cooling unit run their
appropriate speed; Integrated control module monitors safety
circuits continuously.
R and Y1/G or Y2/G thermostat contacts open, completing
the call for cool.
Outdoor fan and compressor are de-energized.
Circulator blower continues running during a cool-off delay
period. The Off delay time and airflow level are determined by
the selected ramping profile.
Electronic air cleaner terminal and circulator blower are
de-energized.
Furnace awaits next call from thermostat.
Fan Only Mode
The normal operational sequence in fan only mode is as follows:
R and G thermostat contacts close, initiating a call for fan.
Integrated control module performs safety circuit checks.
Circulator blower is energized on continuous fan speed (30%
of the furnace’s maximum airflow capability) following a
5-second delay. Electronic air cleaner terminal is energized.
Circulator blower runs; integrated control module monitors
safety circuits continuously.
R and G thermostat contacts open, completing the call for
fan.
Electronic air cleaner terminal and circulator blower are
de-energized.
Furnace awaits next call from thermostat.
Operational Checks
Burner Flame
The burner flames should be inspected with the burner
compartment door installed. Flames should be stable, soft and
blue (dust may cause orange tips but must not be yellow). The
flames must extend directly outward from the burner without
curling, floating or lifting off. Flames must not impinge on the
sides of the heat exchanger firing tubes.
Burner Flame
Check the burner flames for good adjustment, a stable, soft and
blue flame that is not curling, floating or lifting off.
SAFETY CIRCUIT DESCRIPTION
General
A number of circuits are employed to ensure proper furnace
operation. These circuits serve to control any potential safety
hazards and serve as inputs in the monitoring and diagnosis of
abnormal function. These circuits are continuously monitored
during furnace operation by the integrated control module.
Integrated Control Module
The integrated control module is an electronic device which, if a
potential safety concern is detected, will take the necessary
precautions and provide diagnostic information through an LED.
Page view 27
1 2 ... 23 24 25 26 27 28 29 30 31 32 33 ... 39 40

Comments to this Manuals

No comments