Whirlpool DryAire LMA1053L Specifications Page 37

  • Download
  • Add to my manuals
  • Print
  • Page
    / 41
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 36
14.0. Outside Air Pre-Heating Requirements
DryAire Systems require that outside air be pre-heated if mixed air temperatures inside the
dehumidifier might fall below 45°F. To determine if an application requires pre-heating of
outside air, follow simple guide.
14.1. Data required:
A. Design return air temperature. (Industry standard is 82F.)
B. Outside air at winter design temperature. Use values as specified by
design engineer, architect, or ASHRAE tables.
C. Total system CFM (dehumidifier unit) and required outside air CFM.
14.2. Determine worst case scenario for Mixed Air Temperature using the following equation:
MAT=(winter temp °F) x (OA CFM) + (return air temp °F) x (system CFM - OA CFM)
(system CFM) (system CFM)
14.3. If Mixed Air Temperature is less than 45°F, then the pre-heating of outside air is required.
Note: Outside air duct must be insulated to prevent condensation which may form
on the exterior of the duct during cold winter months.
14.4. Example: DRY-30-230-1 dehumidifier (2200 system CFM)
Pool Room Project, 400 CFM of outside Air.
Location, St. Paul, MN. winter temperature condition -16°F.
MAT = (-16°F) x 400 cfm + 82°F x (2200 unit cfm - 400 cfm) = 64.1°F.
2200 cfm 2200 cfm
Conclusion: No need to pre-heat outside air cfm.
15.0. Compressor Failure
Some compressors fail because they are mechanically flawed, most failures are due to system
related problems. Compressor failure can be caused by air or moisture in the refrigerant system,
solid contaminant’s, excessive heat liquid flood back or electrical service malfunctions. To avoid
repeated callbacks, you must determine the cause of the failure and then correct it.
If the compressor failed because its motor has burned out, the refrigerant, oil, and piping may have
become severely contaminated. If a burnout has occurred, use the following procedure to replace
the compressor and clean the refrigerant system.
DryAire Systems 36
Page view 36
1 2 ... 32 33 34 35 36 37 38 39 40 41

Comments to this Manuals

No comments